Low voltage – XLPE insulation cable 0.6/1 kV

$0.00

Application

The Low voltage – XLPE insulation cables with cross-linked polyethene armour with galvanized iron wires are widely used in

industrial and civil power distribution.

Construction

Manufactured according to standard IEC 60502-1

Copper conductor, round standard or Shaped, Class 2 to EC 60228.

For smaller sizes, a solid round conductor, Class 1 as per EC 60228 can also

be supplied upon request.

Insulation – XLPE compound as per IEC 60502 rated for 90°C

continuous operation.

Inner sheath – PVC compound

Armour – Al wires twisted concentrically

Sheath – PVC compound

Category: Tag:

Description

Technical Data

Max. conductor temperature +90° C continuous operation

Max. short circuit temperature 160° C /100h/per year mах.

Rated voltage uo/u – 0.6/1 kV

Test voltage – AC -5min.between cores – 3.5 kV between core and screen –3.5 kV

Bending radius

Single-core – 20 cable diameter, Multicore – 15 cable diameter

Color Coding Scheme

1 Core: Red or Black

2 Cores: Red, Black

3 Cores: Red, Yellow, Blue

4 Cores: Red, Yellow, Blue, Black,

5 Cores: Red, Yellow, Blue, Black, Green

More than 5 cores: Black Cores with White numbers

Nominal Cross Section 

mm2 

Conductor 

Construction 

No./mm 

Nominal Insula­tion Thickness 

mm 

Nominal Sheath Thickness 

mm 

Overall Diameter 

mm 

Cable Weight 

Kg/Km 

1×25 

6.3 

0.9 

1.4 

11.7 

300 

1×35 

7.4 

0.9 

1.4 

13 

390 

1×50 

8.8 

1.4 

15.1 

530 

2×25 

6.3 

0.9 

1.8 

21 

680 

2×35 

7.4 

0.9 

1.8 

23 

890 

2×50 

8.8 

1.8 

21 

1090 

3×25 

6.3 

0.9 

1.8 

22 

920 

3×35 

7.4 

0.9 

1.8 

24 

1230 

3×50 

8.8 

1.8 

25 

1570 

4×25 

6.3 

0.9 

1.8 

24 

1210 

4×35 

7.4 

0.9 

1.8 

28 

1600 

4×50 

8.8 

1.9 

28 

2060 

5×25 

6.3 

0.9 

1.8 

26 

1470 

5×35 

7.4 

0.9 

1.8 

30 

1990 

5×50 

8.8 

32 

2620