Description
Technical Data
Max. conductor temperature +90° C continuous operation
Max. short circuit temperature 160° C /100h/per year mах.
Rated voltage uo/u – 0.6/1 kV
Test voltage – AC -5min.between cores – 3.5 kV between core and screen –3.5 kV
Bending radius
Single-core – 20 cable diameter, Multicore – 15 cable diameter
Color Coding Scheme
1 Core: Red or Black
2 Cores: Red, Black
3 Cores: Red, Yellow, Blue
4 Cores: Red, Yellow, Blue, Black,
5 Cores: Red, Yellow, Blue, Black, Green
More than 5 cores: Black Cores with White numbers
Nominal Cross Section mm2 |
Conductor Construction No./mm |
Nominal Insulation Thickness mm |
Nominal Sheath Thickness mm |
Overall Diameter mm |
Cable Weight Kg/Km |
1×25 |
6.3 |
0.9 |
1.4 |
11.7 |
300 |
1×35 |
7.4 |
0.9 |
1.4 |
13 |
390 |
1×50 |
8.8 |
1 |
1.4 |
15.1 |
530 |
2×25 |
6.3 |
0.9 |
1.8 |
21 |
680 |
2×35 |
7.4 |
0.9 |
1.8 |
23 |
890 |
2×50 |
8.8 |
1 |
1.8 |
21 |
1090 |
3×25 |
6.3 |
0.9 |
1.8 |
22 |
920 |
3×35 |
7.4 |
0.9 |
1.8 |
24 |
1230 |
3×50 |
8.8 |
1 |
1.8 |
25 |
1570 |
4×25 |
6.3 |
0.9 |
1.8 |
24 |
1210 |
4×35 |
7.4 |
0.9 |
1.8 |
28 |
1600 |
4×50 |
8.8 |
1 |
1.9 |
28 |
2060 |
5×25 |
6.3 |
0.9 |
1.8 |
26 |
1470 |
5×35 |
7.4 |
0.9 |
1.8 |
30 |
1990 |
5×50 |
8.8 |
1 |
2 |
32 |
2620 |